Made of naturally degradable materials, the gas box does not contain SF6 gas, and all materials meet the requirements for recyclable and reusable use
The core unit (gas box) adopts a special epoxy resin for the main circuit, which is processed by advanced integrated special sealing technology to achieve a protection level of up to IP67
The main busbar connection is located at the top of the gas box, forming an independent metal enclosed busbar chamber on the cabinet. The main busbar connection is arranged longitudinally in three phases, making it easy to install and expand
Complete logic and mechanical interlocking system, integrated with mechanical switch position indication and panel simulation diagram
Fully insulated, fully shielded, plug-in cable, maintenance free, easy to install
Technical parameter
Serial number | Name | Unit | Main technical parameters | |
1 | Rated insulation level | Rated voltage | kV | 12 |
2 | Rated short-time power frequency withstand voltage | -Alternating, relative to each other | kV | 42 |
-Isolation fracture | kV | 48 | ||
3 | Rated impulse withstand voltage | -Alternating, relative to each other | kV | 75 |
-Isolation fracture | kV | 85 | ||
4 | Rated frequency | 50/60Hz | ||
5 | Rated current | Busbar (standard) | A | 630A |
Busbar (optional) | A | 1250A | ||
6 | Altitude | m | ≤4000 | |
7 | Wind speed | m/s | <34 | |
8 | Earthquake intensity | Not exceeding 8 degrees | ||
9 | Installation and operation site | Places without fire, explosion, chemical corrosion, and severe vibration |